INSTRUCTIONS FOR

20 AMP RECEIVER

Note: The Controller must be powered on while linking. After linking, the Controller retains all settings in the event of power loss. Link up to 25 devices.


SIMPLE LINKING
Use Simple Link Mode for common applications:
1. HOLD the MENU button until the relay clicks (about 5 seconds), then release. The receiver will toggle a steady pattern indicating Simple
Link Mode is active: — — — —
2. TRANSMIT ​the Link Signal by triple pressing the top button on switches or single pressing the Link (or teach) button on sensors.
Relay pauses in ON position for 3 seconds when the link is created, then toggling resumes. Link additional transmitters (up to 25) as
needed. (Relay pauses in OFF position for 3 seconds when the link is deleted.)
3. WAIT​30 seconds for Link Mode to exit automatically (toggling stops).


SIMPLE LINK MODE OPERATING BEHAVIOR
● Manual Switch Control ​(top button ON / bottom button OFF, hold to dim)​: Link any switch.
● Motion Sense Auto ON / Auto OFF​: Link only Occupancy sensors.
● Manual Switch ON / Motion Sense Auto OFF:​ Link both Occ. Sensors & Switches.
● Window/Door Sensor​: Closed ON / Open OFF.
● Key Card Control:​Card in ON, Card out OFF
● Control Transmitter​: ON and OFF.
● Master Dimming Control​: Link an Area Controller with 0­10V input as master.
RANGE:
50-150 FT (typical)
FREQUENCY:
902 MHz
POWER SUPPLY INPUT RATING:
100-277 VAC 50/60 Hz
OUTPUT:
20A Latching Form A Relay w/ Arc Suppression
MAX LOAD:
General Duty: 20A
Tungsten (Incand.): 20A
Fluorescent Ballast: 20A
Motor Load: 1HP
MEMORY:
LINK UP TO 10 SWITCHES
OPERATING TEMP:
-32° to 122°F (0° to 50°C)
DIMENSIONS:
​2.11 x 1.73 x 1.09 inches (54 x 44 x 28 mm)
CERTIFICATIONS:
ETL: UL 60730 (U.S.)
ETL: CSAc22.2#14­05 (Canada)
CE: IEC 60730
ETL: UL 2043 (Plenum)
IEC61000­4­5 (Surge)
FCC: SZV­STM300U (United States)
IC: 5713A­STM300U (Canada)

TEST FUNCTION:

Press and release the SELECT button to toggle Relay ON and OFF.


SENSOR LINK TEST MODE
After linking, press the Link button on a sensor 6 times to activate the Link Test Mode. Subsequent presses from any linked sensor will cause the relay to toggle confirming the sensor is linked and testing the reliability of wireless communications. Link Test Mode will time
out after 60 seconds of no activity.


CLEAR ALL LINKS
1. Activate Simple Link Mode by holding the MENU button until the Controller starts toggling.
2. Hold the SELECT button for 10 seconds to Clear All Links from the Controller.


SELECTIVE LINK DELETION
To remove one Link from Controller and leave others unaffected:
1. HOLD the MENU button to activate Link Mode. The toggling output confirms Link Mode is active.
2. TRANSMIT ​the Link Signal by triple pressing the top button on switches or single pressing the Link (or teach) button on sensors. Relay pauses in OFF position for 3 seconds when the link is deleted, then toggling resumes. 3. WAIT 30 seconds for Link Mode to exit automatically (toggling stops).


REPEATER MODE
Repeater function is DISABLED by default and may be enabled on specific controllers to extend the range by retransmitting all packets 1 or 2 times. Repeater mode may be changed using Advanced Setup instructions.
Transmit ­ ­> Repeater 1x ­ ­> Repeater 2x ­ ­> Receive

ADVANCED SETUP
Advanced Setup uses the Status LED to navigate a hierarchy of menus with blink patterns in one of 3 colors: Amber, Green, and Red. The relay output does not toggle while using Advanced Setup. Navigation overview:
     1. Hold MENU button 15 seconds until Status LED blinks Amber pattern.
     2. Press SELECT button to cycle through blink count options.
     3. Press MENU button to enter/save menu item.
     4. Hold MENU for 5 seconds to exit menu option.
1 ‐ ACTIVATE ADVANCED SETUP
     A. Hold MENU button 15 seconds​until Status LED blinks Amber pattern.
     B. Jump to 2 ­ Link Mode ​or 3 ­ Setup.
2 ‐ LINK MODE: AMBER MENU BLINKS 1‐5
     A. Press SELECT button​to cycle blink count and choose a Link Mode. Different devices may be linked in different modes.
     B. Transmit Link Signal​with fast triple press of switch button or single press of Link button on sensors. Status LED will pause Green when
          link is added. If Link Signal is transmitted a second time, Status LED will pause Red indicating link is removed.
     C. Optional ­ Press MENU button​to see Green blinks indicating number of devices linked in the active mode. Red blink means no devices
          linked. Hold MENU button 5 seconds​to return to Amber Menu.
     D. Wait 60 seconds ​or hold MENU button for 5 seconds to return to Operating Mode.
3 ‐ SETUP: AMBER MENU BLINKS 6‐7
     A. Press SELECT button​to cycle to Config (6 Amber blinks) options.
     B. Press MENU button ​to activate Green Menu.
     C. Press SELECT button​to cycle through Green blink options.
     D. Press MENU button ​to activate Red Menu.
     E. Press SELECT button ​to cycle through Red blink options or hold SELECT button to adjust level if applicable.
     F. Press MENU button​to save selection.
     G. Hold MENU button for 5 seconds​to return to Green Menu.
     H. Hold MENU button for 5 seconds​to return to Amber Menu.
     I. Hold MENU button for 5 seconds​to exit to Operating Mode or power cycle or wait 60 seconds to exit.