INSTRUCTIONS FOR
20 AMP ON/OFF RECEIVER
Note: The receiver must be powered on while linking. After linking, the receiver retains all settings in the event of power loss. Link up to 25 devices.
SIMPLE LINKING
Use Simple Link Mode for common applications:
1. HOLD the LINK button until the receiver clicks (about 5 seconds), then release. The receiver will toggle a steady pattern indicating Simple Link Mode is active: — — — —
2. TRANSMIT the Link Signal by triple pressing the top button on switches or single pressing the Link (or teach) button on sensors. Receiver pauses in ON position for 3 seconds when the link is created, then toggling resumes. Link additional transmitters (up to 25) as needed. (Receiver pauses in OFF position for 3 seconds when the link is deleted.)
3. WAIT 30 seconds for Link Mode to exit automatically (toggling stops).
SIMPLE LINKING MODE BEHAVIOUR
● Manual Switch Control (top button ON / bottom button OFF, hold to dim): Link any switch.
● Motion Sense Auto ON / Auto OFF: Link only Occupancy sensors.
● Manual Switch ON / Motion Sense Auto OFF: Link both Occ. Sensors & Switches.
● Window/Door Sensor: Closed ON / Open OFF.
● Control Transmitter: ON and OFF.
● Master Dimming Control: Link an Area Controller with 0-10V input as Master.
● Other Functionality: See chart for details

RANGE: | 50-150 FT (typical) |
FREQUENCY: | 902 MHz |
POWER SUPPLY INPUT RATING: | 100-277 VAC 50/60 Hz |
OUTPUT: | 20A Latching Form A Relay w/ Arc Suppression |
MAX LOAD: | General Duty: 20A Tungsten (Incand.): 20A Fluorescent Ballast: 20A Motor Load: 1HP |
MEMORY: | LINK UP TO 10 SWITCHES |
OPERATING TEMP: | -32° to 122°F (0° to 50°C) |
DIMENSIONS: | 2.11 x 1.73 x 1.09 inches (54 x 44 x 28 mm) |
CERTIFICATIONS: | ETL: UL 60730 (U.S.) ETL: CSAc22.2#1405 (Canada) CE: IEC 60730 ETL: UL 2043 (Plenum) IEC6100045 (Surge) FCC: SZVSTM300U (United States) IC: 5713ASTM300U (Canada) |
TEST FUNCTION
Press and release the TEST button to toggle Receiver ON and OFF.
CLEAR ALL LINKS
Activate Simple Link Mode by holding the LINK button until the Receiver starts toggling.
Hold the TEST button for 10 sec to Clear All Links from the Receiver.
SELECTIVE LINK DELETION
To remove one Link from Receiver and leave others unaffected:
HOLD the LINK button to activate Link Mode. The toggling output confirms Link Mode is active.
TRANSMIT the Link Signal by triple pressing the top button on switches or single pressing the Link (or teach) button on sensors. Receiver pauses in OFF position for 3 seconds when the link is deleted, then toggling resumes.
WAIT 30 seconds for Link Mode to exit automatically (toggling stops).
REPEATER MODE
Repeater function is DISABLED by default and may be enabled on specific receivers to extend the range by retransmitting all packets 1 or 2 times. Repeater mode may be changed using Advanced Setup instructions. Transmit > Repeater 1x > Repeater 2x > Receive
ADVANCED SETUP
Advanced Setup uses the Status LED to navigate a hierarchy of menus with blink patterns in one of 3 colors: Amber, Green, and Red. The receiver output does not toggle while using Advanced Setup. Navigation overview:
Hold LINK button 15 sec until Status LED blinks Amber pattern.
Press TEST button to cycle through blink count options.
Press LINK button to enter/save menu item.
Hold LINKfor 5 sec to exit menu option.
1 - ACTIVATE ADVANCED SETUP
A. Hold MENU button 15 sec until Status LED blinks Amber pattern.
B. Jump to 2 Link Mode or 3 Setup.
2 ‐ LINK MODE: AMBER MENU BLINKS 1‐5
A. Press TEST button to cycle blink count and choose a Link Mode. Different devices may be linked in different modes.
B. Transmit Link Signal with fast triple press of switch button or single press of Link button on sensors. Status LED will pause Green when link is added. If Link Signal is transmitted a second time, Status LED will pause Red indicating link is removed.
C. Optional Press LINK button to see Green blinks indicating number of devices linked in the active mode. Red blink means no devices linked. Hold LINK button 5 sec to return to Amber Menu.
D. Wait 60 sec or hold LINK button for 5 sec to return to Operating Mode.
3 ‐ SETUP: AMBER MENU BLINKS 6‐7
A. Press TEST button to cycle to Config (6 Amber blinks) options.
B. Press LINK button to activate Green Menu.
C. Press TEST button to cycle through Green blink options.
D. Press LINK button to activate Red Menu.
E. Press TEST button to cycle through Red blink options or hold TEST button to adjust level if applicable.
F. Press LINK button to save selection.
G. Hold LINK button for 5 sec to return to Green Menu.
H. Hold LINK button for 5 sec to return to Amber Menu.
I. Hold MENU button for 5 sec to exit to Operating Mode or power cycle or wait 60 sec to exit.