INSTRUCTIONS FOR
BASIC DIMMING SWITCH KITSALL KITS COME PRE-LINKED, ONLY DO THIS TO ADD OR REMOVE SWITCHES OR CONTROLLERS
RESET DIMMING RECEIVER:
Using the CLEAR button can reload the controller to the factory pre-commissioned settings with linked devices OR it can load the factory default parameters and remove all linked devices.
• To return the controller to the factory pre-commissioned state, press the CLEAR button until the red POWER and green LEARN LEDs start blinking, approximately 5 seconds. Release the button and the red POWER LED will begin blinking indicating the factory commissioned pre-linked devices.
• To completely clear the controller returning it to factory default settings removing all linked devices, press the CLEAR button until the red POWER and green LEARN LEDs come on solid, about 15 seconds, then release. The POWER LED will stay ON solid indicating the factory default state.
LINKING FOR DIMING RECEIVER:
1. Press the button marked LEARN for a half second. In link mode the LEARN LED will stay ON and the POWER LED will toggle every 2 second.
2. Using the switch that will be linked to the controller, press the wall switch ON three times. If linking a sensor, press the sensors TEACH or LINK button, refer to the sensor documentation. The POWER LED will remain lit for 4 seconds while it links the new device. It will resume toggling allowing you to link another device up to a total of 20 devices. To exit link mode, press the LEARN button on the controller again for a half second.Note: Link mode will time out after no activity in thirty seconds.
RANGE: | 80-330 FT (typical) |
FREQUENCY: | 902 MHz |
POWER SUPPLY INPUT RATING: | 120 VAC 50/60 Hz |
RELAY OUTPUT: | 1 FORM A RELAY 10A |
MAX LOADS : | 600W (5A) |
LOAD TYPES: | Tungsten lamps 2-wire Fluorescent ballasts Line voltage LED drivers |
OPERATING TEMP: | 32°F to 122°F (0-50 °C) |
DIMENSIONS: | 2.75(H) x 3(L) x 3.5(W) inches |
CERTIFICATIONS: | CEC Title 24 compliant ETL Listed Component Conforms to UL Standard 508 Certified to CAN/CSA Std C22.2 No.14 UL 2043 Plenum rated FCC Part 15.231 Contains FCC ID: SZV-STM300U IC RSS-210 |
LED Blink Codes and Operation
If the controller was factory pre-commissioned, upon power up it will immediately begin blinking the red POWER LED based on the type and count of linked devices. The type is indicated by long blinks followed by short blinks counting the number of devices linked. This pattern will repeat after a short pause.
If the controller was factory pre-commissioned, upon power up it will immediately begin blinking the red POWER LED based on the type and count of linked devices. The type is indicated by long blinks followed by short blinks counting the number of devices linked. This pattern will repeat after a short pause.
MANUALLY CONFIGURE DIMMING MODE
The dimming mode for the ER6CD-AU-120 Phase Adaptive Dimmer is detected automatically by default. The dimming mode for the ER6CD-AU-277 is reverse phase by default. At the device, you can change the dimming mode manually, entering forward phase, reverse phase, or automatic phase dimming.1. Simultaneously, press and hold the “Learn” and “Clear” buttons for five seconds, then release. The CLR/LRN and Status LEDs will begin to flash. The LEDS indicate which dimming mode is active.
• Both Green: Forward Phase dimming
• Both Red: Reverse Phase dimming
• If the dimmer is in Automatic dimming mode, the Status LED will flash amber, and the CLR/LRN LED will indicate the current mode with specific LED colors. (red is Reverse Phase dimming mode and green is Forward Phase dimming mode).
2. To change the current mode, press and hold the “Learn” and “Clear” buttons until the LEDs change to the desired dimming mode according to the LEDs state.
Note: The device will return to normal operation, exiting the dimming mode menu, 10 seconds after the last interaction.